SDC / DHC
1.4
Electric installation
All electrical connections must be carried out by qualified personnel.
1.5
Cable dimensions
1.5 mm² for all 230 V cable (power supply, burner, pumps, actuators).
0.5 mm² for sensors, selectors , bus and analogue in- and outputs.
0,6 mm² for bus wiring (recommended: J-Y(St)Y2x0,6)
1.6
Maximum cable length
Sensors selectors and analogue inputs
A maximum cable length of 200 meters is recommended. Longer distances are
possible but increase the risk of interferences.
Relay outputs
Unlimited cable length.
Bus connections
A maximum cable length of 100 meters from the first to the last member of the
bus (incl. wall modules) is strongly recommended.
1.7
Cable installation
Cables for 230 V must be installed separate from low voltage (sensor selector
bus) cables.
1.8
Cabinet earth and ground
Please install and connect the controllers according to local rules and standards.
1.9
Domestic hot water higher than 60 degrees C
WARNING Please note that in the following cases there is a danger at hot
MU1H-0207GE51 R1206
water tabs (kitchen, bath). In order to avoid scalding please mix
enough cold water.
22