Smoke alarm devices are to be used as the bare minimum
bedrooms, children's rooms and hallways which act as escape routes, and are
to be installed in each case in the middle of the room, on the ceiling only (do not
install on a wall) (Fig. 2). Select the highest installation location with a minimum
distance of 50 cm to surrounding walls, furniture and lamps. In the case of
sloping ceilings with an angle of over 20°, detectors should be installed 0.5 - 1 m
away from the highest point. Configuration is optimal
located in all other rooms as well as staircases. In washrooms (bathrooms,
lavatories etc.), a smoke alarm device is generally not necessary because the
risk of fire is low.
Please note the graphics in this manual and the detailed information available in
the EN14676 standard
apartments and rooms with similar purposes – Installation, use and
maintenance".
Special installation cases
Installation in a hallway with a width of < 3 m
Maximum distance from the front
walls: 7.5 m
Maximum distance between
detectors: 15 m
Installation on the mitre line between
intersecting crossings, T-junctions
and corner areas
"Smoke alarm devices for use in residential buildings,
12
equipment in all
RM
when devices are
RM