Installation - Siemens DMA1133D Montageanleitung

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
en

Installation

Use
· Manual call point 'indirect activation' for the AlgoRex fire
detection system (Fig. 1)
· Model DM1103D compatible with fire detection
systems with collective/SynoLINE600 signal processing
· Model DM1133D compatible with
AnalogPLUS/SynoLOOP fire detection systems
· Model DM1153D compatible with CS11 interactive fire
detection system
Installation
1. The line test is complete.
2. Remove the minus − minus bridge (AnalogPLUS,
SynoLOOP, interactive, only necessary for line test)
(Fig. 5 [6]).
3. Latch the corresponding
DMA1103D/DMA1133D/DMA1153D switching unit
(Fig. 2) into the connected DMA1192 housing and
screw it tightly in place.
4. Insert the country-specific label.
Installation in wet areas
1. Place the additional seal (Fig. 3, optional) over the
switching unit (protection category IP65).
2. Close the door.
2
Building Technologies
Fire Safety
DMA1103D installation in an Ex area
WARNING
Incorrect usage of the manual call points
Risk of explosion caused by incorrect planning or
installation of the manual call points
· Before you install the manual call points, it is
absolutely essential that you observe the
information in document 001204 'Fire alarm
signal in areas at risk of explosion'.
WARNING
Electrostatic charging of the housing
Risk of explosion
The DMA1103D manual call point may only be
used in potentially explosive areas if, after
mounting and installation,
the 'Avoid electrostatic charging' sticker is
attached to the housing so that it is clearly visible.
WARNING
Incorrect cleaning and maintenance of alarm
indicators
Risk of explosion
· Avoid electrostatically charging the devices
during cleaning and maintenance.
· Do not use solvents.
1. Attach the 'Avoid electrostatic charging' sticker to the
housing so that it is clearly visible. The sticker comes
with the switching unit (Fig. 2 [1]).
Connection diagram DMA1103D
collective/SynoLINE600
- See Fig. 4.
Connection diagram DMA1133D, DMA1153D
AnalogPLUS/SynoLOOP, interactive
- See Fig. 5.
Final work/Checking
· Function test:
Open door, press alarm button firmly: LED flashes
· To deactivate: Push the release lever to the right with a
screwdriver (Fig. 6).
· Close the door.
WARNING
Until they are finally commissioned, all manual
call points must remain labeled as "NOT IN
USE".
If necessary: Install the protective cover (accessories)
(Fig. 7).
001720_g_--_--
2016-04-2016