Fault cause
Pressure gauge indicates
incorrect values or is not
working at all.
Abnormal flame pattern of
non-adjustable pressure
regulator
Abnormal flame pattern
of adjustable pressure
regulator

MAINTENANCE

It is advisable to check the system with the pressure regulator for leaks and to ensure that it is
functioning properly occasionally, such as once per year.

REPLACEMENT

If there is any sign of wear or if the product or parts thereof are damaged, it must be replaced.
When the product has been replaced, observe the steps ASSEMBLY, LEAK TESTING and
START-UP.
To ensure that the installation works faultlessly under normal operating conditions, it is
recommended that you replace the device within 10 years of the date of manufacture.
In commercial applications, according to DGUV regulation 79, parts of consumer
units that are subject to wear and ageing* must be replaced after 8 years. This does not apply
if the proper condition has been confirmed by an expert.
* System parts that are subject to wear or ageing are, for example, membranes, automatic
and manual changeover valves, pressure regulators, hoses assemblies.
Product damaged due to flooding!
This causes corrosion and malfunctions to the pressure regulator.
Replace the pressure regulator following flooding!

RESTORATION

If the actions described in TROUBLESHOOTING do not lead to a proper restart and if there is
no dimensioning problem, the product must be sent to the manufacturer to be checked. Our
warranty does not apply in cases of unauthorised interference.
part no. 01 267 50 c
Medium pressure regulator type VSR 0126
Action
Pressure gauge is defective.
 Replace only when the LPG system is completely
de-pressurised.
Compare the nominal outlet pressure with the nominal
connection pressure:
 if they do not correspond, replace the pressure regulator
or the gas appliance
Measure the outlet pressure; outlet pressure is not within
the specified limits:
 check the system configuration
 pressure regulator is defective, replace
 check the gas filter
Compare the nominal outlet pressure of the pressure
regulator with that of the connected device:
 If they do not match, adjust the pressure regulator to the
nominal connection pressure
Measure the outlet pressure of the pressure regulator;
outlet pressure is not within the specified limits.
 Check the system configuration
 Readjust the outlet pressure