Herunterladen Inhalt Inhalt Diese Seite drucken

Status Messages - Balluff BMD 1L serie Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1

Status messages

Display and adjustment module
Further echo curves: Up to 10 echo curves can be stored in a ring
PC with PACTware/DTM
Control system with EDD
Display and adjustment module
9.3
Status messages
The instrument features self-monitoring and diagnostics according to
NE 107 and VDI/VDE 2650. In addition to the status messages in the
following tables, detailed error messages are available under menu
item "Diagnostics" via the display and adjustment module, PACTware/
DTM and EDD.
The status messages are divided into the following categories:
Failure
Function check
Maintenance requirement
and explained by pictographs:
1
Fig. 22: Pictographs of the status messages
1
Failure - red
3
Function check - orange
4
Maintenance - blue
Failure: Due to a malfunction in the instrument, a fault message is
outputted.
This status message is always active. It cannot be deactivated by the
user.
Function check: The instrument is being worked on, the measured
value is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Out of speci cation: The measured value is unreliable because an
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Maintenance:
still valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
9 Diagnostics and servicing
2
3
4
53

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis