Installation and Operating Specification EUR EC
Controller Setup
20 %
nmin at Group2
Controller Setup
70 %
Group 3 ON value
Controller Setup
65 %
OFF Value Group3
Controller Setup
30 %
nmin at Group3
Controller Setup
85 %
Group 4 ON value
Controller Setup
80 %
OFF Value Group4
Controller Setup
40 %
nmin at Group4
* Display as long as no group assignment via analogue output, relay, MODBUS:
Higher settings must be selected for following groups and the switch-off value of the group must be
below the switch-on value.
L-BAL-E274-GB 1815 Index 002
nmin at Group2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 20 % *
Group 3 ON value
Switch-on value for Group3
Setting range: 0 - 100 %
Factory setting: 70 % *
OFF Value Group3
Switch-off value for group3
Setting range: 0 - 100 %
Factory setting: 65 *
nmin at Group3
Minimum Value for Group3
Setting range: 0 - 100 %
Factory setting: 30 % *
Group 4 ON value
Switch-on value for Group4
Setting range: 0 - 100 %
Factory setting: 85 % *
OFF Value Group4
Switch-off value for group4
Setting range: 0 - 100 %
Factory setting: 80 % *
nmin at Group4
Minimum Value for Group4
Setting range: 0 - 100 %
Factory setting: 40 % *