Pressure reading for verifi cations
P2 = L pressure port
P1 = H pressure port
Actuator components and functionality
Flow is preset using the built-in actuator.
When fi rst powered on, "GO 0" is displayed in the LCD display. At this point,
wait for "0" to appear.
Pressing the MODE button for 2 seconds or longer will switch to setting
mode. From here, it is then possible to select the detail indication suitable
for your on-site installation.
When in "set" mode, pressing the button again will permit you to select
another set mode (S-01 - S-12).
Actuator settings
Set
Setting
Select input /
indication type
Input tool selection
Min. fl ow setting
2
P1 - P2
Indication
Defi nition
Flow input
% input
Voltage input
Voltage input
Current input
Current input
On/ Off input
3-point
fl oating input
PWM 5 s.
PWM 25 s.
Internal input
Minimum fl ow
Min. fl ow setting
setting to display
If P1-P2 > start-up pressure, then the valve is within
the working range (see technical data).
Q
Q≠CONST
Q=CONST
START-UP
PRESSURE
30 kPa
Operation
Explanation
Control by INT mode volume
Finish by pressing MODE
button after selection
Control by INT mode %
Set by voltage JOG
Pin3-Pin1 voltage: 0...10 V
Set by voltage JOG
Pin3-Pin1 voltage: 2...10 V
Set by current JOG
Pin3-Pin1 current: 0...20 mA
Set by current JOG
Pin3-Pin1 current: 4...20 mA
24 V: Open
Pin3-Pin1 voltage. 24 V: Open
0 V: Close
Open or 0 V: Close
Pin3-Pin1 voltage. 24 V: Open
P3 24 V: Open
Pin4-Pin1 voltage. 24 V: Close
P4 24 V: Close
PWM 0.1...5.0 s
0.1 s: 0 %, 5 s: 100 %
PWM 0.1...25 s
0.1 s: 0 %, 25 s: 100 %
Set using buttons
Set via buttons on actuator
Finish by pressing MODE
Min. fl ow should be lower
button after selection
than max. fl ow
Table continued on next page
P1 - P2
1
2
1
Display
3
2
UP (
) button
4
3
MODE button
4
DOWN (
) button