Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection - WIKA WUC-1 Serie Betriebsanleitung

Ultra high purity transducer
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7. Starting, operation

Electrical connection

WARNING!
Connect the enclosure to ground through the process connection, against electromagnetic fields and electro-
static discharge.
WARNING!
Specific conditions for safe use in explosive atmosphere
External earthing connection shall be established by end-user via pressure connection minimum 4 mm²
required. External earthing connection shall be corrosion resist and locked against rotation.
The connector provided by the end user in the end use application shall be in accordance with all applicable
clauses of IEC 60079-0 and IEC 60079-15. A minimum degree of protection IP54 according to IEC 60529 shall
be ensured.
Cable provided by end-user shall be suitable for the ambient temperature.
The Sub-D version has to be installed in a way that it is protected against an impact energy > 4 J. The connec-
tor as well as the corresponding sealing are provided by the end user in the end use application and shall be
in accordance with all applicable clauses of IEC 60079-0 and IEC 60079-15. A minimum degree of protection
IP54 according to IEC 60529 shall be ensured.
For use under NEPSI conditions:
- The connector provided by the end user in the end use application shall be in accordance with all applicable
clauses of GB3836.1-2010 and GB3836.8-2003. A minimum degree of protection IP 54 shall be ensured.
- Obey the warning "Do not separate when energized".
WIKA Operating instructions / Betriebsanleitung WUC-1x
EN
11

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Wuc-10Wuc-15Wuc-16

Inhaltsverzeichnis