Installation Guide
Connecting more
Danfoss Icon™
Master Controllers in
a system
Test procedures for
multiple Danfoss
Icon™ Controllers in a
system
© Danfoss | FEC | 2019 .01
Danfoss Icon™ Master Controller 24 V
If wired system
Connect up to three Danfoss Icon™ Master
Controller 24V to each other with a 4-wire twisted
pairs cable and the supplied connector .
4 (2 x twisted pairs)
Cable pin out
1
2
3
1 . GND
2 . COM A
3 . COM B
NET TEST on System Slave
1 . Install all thermostats and actuators as
described in the Quick Guide D2 to D6 .
2 . Perform Network test . Press
and press
to choose NET TEST . Confirm
with OK (Quick Guide E7 and E8) .
3 . After completing the TEST press
RUN mode and press OK (Quick Guide E9) .
APP TEST on System Master
1 . Perform application test . Press
TEST and press
to choose APP TEST .
Confirm with OK (Quick Guide E7 and E8) .
2 . After completing the TEST press
RUN mode and press OK (Quick Guide E9) .
Note! If an Expansion Module is added to the system,
it must be installed on the Master Controller.
If wireless system
Wireless connection of up to three Danfoss Icon™
Master Controllers 24V requires a Radio Module
with each Master / Slave .
Connecting procedure for multiple Danfoss
Icon™ Controllers in a system
On System Master
Max. 3 x Master
Controllers in one
1 . Install all thermostats and thermal actuators as
system.
described in the Quick Guide D2 to D6 .
2 . Perform network test . Press
and press
witk OK (Quick Guide E7 and E8) .
Pairing Master and Slave
Note! Slave Controllers must be assigned as System
Slaves before assigning outputs and thermostats to
them.
1 . On the selected system master, press
select INSTALL mode .
2 . On the system slave, press and hold
1 .5 sec . The display now toggles between
SLA TYPA and SLA TYPB .
3 . Press
types and confirm with OK . See "Slave type
definition" on the next page .
4 . Repeat step 4 and 5 to assign a 2
Controller to the system (max . two slaves are
permitted) .
Changing Slave type
On Danfoss Icon™ Slave Controller press and
1 .
hold
to select TEST
between SLA TYPA and SLA TYPB .
2 .
Press
types and confirm with OK . See "Slave type
to select
definition" for more information .
LINK test on Slave (between Master and Slave)
Press
for 1 .5 sec . The display shows inclusion
to select
pattern while making the LINK test . When done, the
display shows the number of packages recieved in
percentage .
to select
to select TEST
to choose NET TEST . Confirm
to choose between the two slave
nd
for 1 .5 sec . The display now toggles
to choose between the two slave
VIMCG30F | 088N3678 | 9
EN
to
for
Slave