Herunterladen Inhalt Inhalt Diese Seite drucken

Danfoss Icon Installationsanleitung Seite 13

Hauptregler 24 v
Vorschau ausblenden Andere Handbücher für Icon:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 14
Installation Guide
© Danfoss | FEC | 2019 .01
Danfoss Icon™ Master Controller 24 V
Master Controller 24V and Expansion Module (optional)
Supply voltage
Supply frequency
Output voltage, actuators
Max . power consumption per actuator output
Number of actuator outputs (1 actuator per output terminal)
Output voltage, thermostats
Stand-by consumption per thermostat
Max . number of thermostats
Max . length of wire from master controller to a 24 V thermostat
(depends on cable type used)
Stand-by consumption, Master Controller
Max . power consumption, excluding use of PWR 1 and PWR 2
outputs
Internal protection (fuse, non-replacable)
Output "Relay"
Actuator outputs, type
Output "PWR 1", type and rated max . output
Output "PWR 2", type and rated max . output
Output "PWR 3" (optional, on Expansion module — used for dew
point sensor)
Input "1" (optional, on Expansion module — use varies acc. to
application chosen)
Input "2" (optional, on Expansion module — use varies acc. to
application chosen)
Input "3", sensor input (optional, on Expansion module)
Dimensions
Conformity declared acc . to following directives
Purpose of control
Method of providing earthing
Encapsulation (IP Class)
Protection class
Ambient temperature range, continious use
Wireless Thermostat
Purpose of control
Ambient temperature range, continious use
Frequency
Transmission power
Encapsulation (IP Class)
Supply voltage
Conformity declared acc . to following directives
Protection class
24V Wired Thermostat
Purpose of control
Ambient temperature range, continious use
Encapsulation (IP Class)
Supply voltage
Conformity declared acc . to following directives
Protection class
External sensor
220-240 VAC
50/60 Hz
24 VDC
2 W
10 or 15 depending on type
24 VDC
0,2 W
10 or 15 depending on type
2
If 2x2x0,6 mm
STP/UTP: 100 m
2
If 2x0,5 mm
: 150 m
2
If > 2x0,75 mm
: 200 m
< 2 W
< 50 W
2,5 A
Micro-disconnection (Type 1 .B action), Max . 2 A load
Electronic disconnection (Type 1 .Y action)
Micro-interruption (Type 1 .C action)
Type: Permanent output, Always live 230 V, Max . 50W
24 VDC, max . 1 W
Ext . switch input (internal 24V pull-up)
Ext . switch input (internal 24V pull-up)
External sensor, PT 1000 (Danfoss ESM 11)
W: 370 mm, H: 100 mm, D: 53 mm
LVD, EMC, RoHS and WEEE
Individual electronic room temperature control
Factory fitted power cord, incl . PE-conductor
IP 20
Class I
0 °C to + 50 °C
Room thermostat for room temperature control
0 °C to + 40 °C
869 MHz
<2 .5 mW
IP 21
2 x 1,5 V AA-Alkaline batteries
RED, RoHS, WEEE
Class III
Room thermostat for room temperature control
0 °C to + 40 °C
IP 21
24 VDC
EMC, RoHS, WEEE
Class III
NTC type, 47 k @ 25 °C (Optional, 088U1110)
VIMCG30F | 088N3678 | 13
EN

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis