CR0301
Analogue inputs
X2:01...10, A_IN 00...A_IN 07
can be configured as ...
Digital inputs
X4:01...08, IN 00...IN 07
can be configured as ...
Digital inputs
X4:11...14, IN 08...IN 11
can be configured as ...
Digital inputs
X4:15...18, IN 12...IN 15
can be configured as ...
Test input
RS 232, D-Sub plug, pin 09
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen
Characteristics of the inputs
■ Voltage inputs
input voltage
0...10 V or 0...32 V
resolution
10 bits
accuracy
± 1% FS
input resistance
78.4 kΩ (0...10 V), 46.6 kΩ (0...32 V)
input frequency
50 Hz
■ Current inputs, with diagnostic capability
input current
0...20 mA
resolution
10 bits
accuracy
± 1% FS
400 Ω
input resistance
input frequency
50 Hz
At a current of > 23 mA the pair of channels is switched to the voltage input!
■ Voltage inputs, 0...32 V, ratiometric
function
(U
÷ U
IN
value range
0...1000 ‰
■ Binary voltage inputs for positive sensor signals
The analogue inputs A_IN 00...07 are configured / switched in pairs!
The following inputs are combined in pairs: 0+4, 1+5, 2+6, 3+7
■ Digital inputs for positive sensor signals, with diagnostic capability
switch-on level
> 0.6 U
switch-off level
< 0.3 U
input resistance
3.21 kΩ
input frequency
50 Hz
■ Digital inputs for positive sensor signals, with diagnostic capability
switch-on level
> 0.6 U
switch-off level
< 0.3 U
input resistance
3.16 kΩ
input frequency
50 Hz
■ Frequency inputs for positive sensor signals, with diagnostic capability
switch-on level
0.4...0.7 U
switch-off level
0.2...0.24 U
input resistance
3.16 kΩ
measuring range
0...2 kHz oder 1...30 kHz
■ Digital inputs for positive sensor signals
switch-on level
> 0.6 U
switch-off level
< 0.3 U
input resistance
3.21 kΩ
input frequency
50 Hz
■ Digital inputs for negative sensor signals
switch-on level
< 0.2 U
switch-off level
> 0.5 U
input resistance
3.21 kΩ
input frequency
50 Hz
The digital inputs IN 12...15 are configured / switched in pairs!
The following inputs are combined in pairs: 12+13, 14+15
During the test mode (e.g. programming) the TEST input must be connected to U
(10...32 V DC).
For the "RUN" mode the TEST input must not be connected.
also see wiring, page 5