Cyclical Output Data - Eaton EMS-...-SWD Serie Handbuch

Elektronischer motorstarter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3.4.2 Cyclical output data

Bit
7
6
Configu-
ration
Bit
Designation
0
SDIR/SDIRR
1
SDIRL
2
RESM
3
RESA
4
5
6
7
If the unit trips due to a motor overload or phase failure, the RESM output bit
can be used to carry out a manual reset after a cool-down period of
2 minutes elapses. The RESM output bit needs to have a rising edge (signal
change from 0 to 1) in order to carry out a manual reset. If the bit maintains a
value of 1 for an extended period of time, the electronic motor starter will
respond with a fault message.
Meanwhile, the RESA output bit can be used to trigger an automatic reset in
the event that the unit trips due to overload or phase failure. The unit will
restart automatically after the cool-down period of 20 minutes elapses.
Electronic motor starter EMS-...-SWD 12/18 MN034002ZU-DE/EN www.eaton.com
5
4
3
RESA
Meaning
Motor start / start clockwise operation
Start anticlockwise operation
Manual reset
Automatic reset
Not used
Not used
Not used
Not used
3 Commissioning
3.4 Cyclic data
2
1
0
RESM
SDIRL
SDIRR
67