3 Commissioning

3.4 Cyclic data

3.4 Cyclic data

3.4.1 Cyclic input data

64
EMS-DOS/ROS-SWD electronic motor starters have a maximum of seven
input bytes and one output byte. The amount of cyclical input data can be
varied by using different data profiles (→ Section 3.6, "Data profiles", Page
71).
Byte 0:
Status information: fault message, operating direction, module status
Bit
7
6
Configu-
SUBST
PRSNT
ration
Bit
Designation
0
ERR
1
DIRR/DIRON
2
DIRL
3
EN
4
DIAG
5
6
PRSNT
7
SUBST
1 Byte
Set rated operational current, trip indication, overload needs to be reset
Bit
7
6
Configu-
ACKR
TRIPR
ration
Bit
Designation
0
Ir
1
Ir
2
Ir
3
Ir
4
TRIPR
Electronic motor starter EMS-...-SWD 12/18 MN034002ZU-DE/EN www.eaton.com
5
4
3
DIAG
EN
Meaning
Fault message
Clockwise operating direction active (EMS-RO-...-SWD) or operating
direction active (EMS-DO-...-SWD
Counterclockwise operating direction active (EMS-RO-...-SWD only)
0: There is no external enable signal present.
1: An external enable signal is present.
0: No diagnostics present
1: Diagnosis present
Not used
0: Module not available
1: Module available
0: Configured module present
1: Universal module M22-SWD-NOP(C) present
5
4
3
TRIPR
TRIPR
Ir
Meaning
Set value Ir
Set value Ir
Set value Ir
Set value Ir
Differential trip indication
2
1
0
DIRL
DIRR/
ERR
DIRON
2
1
0
Ir
Ir
Ir