8.2
Maintenance intervals
When
Annually
After an alarm condition Perform a function test after each alarm (see
If required
Maintenance
Activity
Perform a function test (see chapter "Function
test").
Check the condensate trap at the product and the
condensate traps installed in the hoses
Drain the condensate traps, if necessary
Replace the filter in the check valve if it is polluted
and tightly screw the condensate trap back into
the housing
If a 9 V battery is fitted for alarm in the case of
power outage, replace the battery
Verify that the product and its environment are
clean, accessible and easy to oversee
chapter "Function test")
Replace the relay fuse F1 (T 2 A)
Eurovac HV
EN