5.4.4
Output
VOLTAGE PEAKS WHEN INDUCTIVE CONSUMERS ARE SWITCHED OFF
When inductive consumers are switched off, this can cause voltage peaks and
can lead to adverse effects on electrical systems and may destroy the switching
contact.
Use commercially available standard RC combinations such as 0.1 µF/
100 Ohm for inductive consumers.
Failure to follow these instructions can result in equipment damage.
The output signal of the product is made available via a voltage-free relay
contact (changeover contact). If no alarm is present, the relay is de-ener-
gised; in case of an alarm, the relay is energised.
1. The relay cable requires permanent installation.
2. Route the relay cable through the upper or bottom cable gland into the
product.
3. Connect the relay cable to the terminals with the corresponding desig-
nations.
4. Verify safe separation of the relay cable.
- The insulation characteristics of the relay cable must at least comply
with IEC 60227 or IEC 60245.
Mounting
NOTICE
Eurovac HV
EN
27