Herunterladen Inhalt Inhalt Diese Seite drucken

Product Description; Pin Assignment - Wieland SP-SDI Gebrauchsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
3

Product description

3.1 Description
3.1.1 Input/Output-expansion module SP-SDIO
The module SP-SDIO is an expansion module within the system
samos®PRO and it provides eight safe inputs and four safe outputs.
Features of the SP-SDIO are:
Monitoring of safety switches and sensors.
Transmission of data to the controller module SP-SCON
Receiving of data from the controller module and switching of the
outputs
Fast Shut Off (direct switching of the outputs without data trans-
mission)
The module SP-SDIO does not operate independently. It operates
only in combination with a controller module SP-SCON, see the
configurations-software samos®PLAN.
The simultaneous use of several modules SP-SDIO is possible (up
to twelve modules SP-SDIO and/or SP-SDI overall in the system).
To supply the safe outputs, each input/output-expansion module
must be connected to an external voltage supply.
The module SP-SDIO provides two test signals for a cross
monitoring on the inputs. One test signal is provided on the test-
output X1, the other test signal is provided on the test-output X2.
SP-SDIO detects short circuits between the two
test-outputs (X1, X2), if the duration of the test
pulses is < 4 ms.
If the duration of the test pulses is 4 ms, short
WARNING
WARNING
WARNING
WARNING
circuits between the test-outputs may remain
undetected.
3.1.2 Input-expansion module SP-SDI
The module SP-SDIO is an expansion module within the system
samos®PRO and it provides eight safe inputs and four safe outputs.
Features of the SP-SDIO are:
Monitoring of safety switches and sensors.
Transmission of data to the controller module SP-SCON
The module SP-SDIO can not operate independently. It operates
only in combination with a controller module SP-SCON; see the
configurations-software samos®PLAN.
The simultaneous use of several modules SP-SDIO is possible (up
to twelve modules SP-SDIO and/or SP-SDI overall in the system).
The supply voltage is provided by the connector of the internal
interface S-BUS+.
The module SP-SDI provides two test signals for a cross
monitoring on the inputs. One test signal is provided on the test-
outputs X1, X3, X5 and X7, the other test signal is provided on the
test-outputs X2, X4, X6 and X8.
SP-SDI detects short circuits between the two
groups of test-outputs (X1, X3, X5, X7) and (X2, X4,
X6, X8), if the duration of the test pulses is < 4 ms.
If the duration of the test pulses is 4 ms, short
WARNING
WARNING
circuits between the two groups of test-outputs may
WARNING
WARNING
remain undetected.
Short-circuits inside of a group of test-outputs (X1, X3, X5, X7) or
(X2, X4, X6, X8) will not be detected.
This has to be observed during the wiring of the safety switches
>
or sensors, e.g. by a separate laying or by shielding the wires.
6 6 6 6
3.2 Indicators
Module Status LED
3.2.1 Indicator MS-LED
MS-LED
Off
red blinking (1 Hz)
green blinking (1 Hz)
green
red/green blinking (1Hz)
☼☼
red
3.2.2 Indicator Input-/Output-LEDs
Input-LEDs (I1... I8)
Output-LEDs (Q1 ... Q4)
(only SP-SDIO)
Off
green
green blinking (1 Hz)
synchronously with
red/green MS-LED
green blinking (1 Hz)
alternately with
red/green MS-LED

3.3 Pin assignment

3.3.1 Pin assignment SP-SDIO
Module
SP-SDIO
3.3.2 Pin assignment SP-SDI
Module
SP-SDI
8 Input LEDs
SP-SDIO
4 Output LEDs
(SP-SDIO only)
Description
Supply voltage is out of range
Selftest, system initialization or
invalid configuraton
Module is ready
Application is executed
Reversible fault
Critical fault in the system
Description
Input / Output is not active
Input / Output is active
Input / Output is not active and
a reversible fault has occurred
Input / Output is active and a
reversible fault has occurred
Terminal
Description
X1
Test-output 1
X2
Test-output 2
I1 ... I4
Inputs 1 to 4
A1
24 V
A2
GND
I5 ... I8
Inputs 5 to 8
Q1 ... Q4
Outputs 1 to 4
Terminal
Description
X1/X3
Test output 1
X2/X4
Test output 2
I1 ... I4
Inputs 1 to 4
I5 ... I8
Inputs 5 to 8
X5/X7
Test output 1
X6/X8
Test output 2

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Sp-sdio

Inhaltsverzeichnis