Circular plug M8 - 4-pole (process actual value) - only Type 8693
input
Wire
pin
configuration
type
color
13)
14)
4 – 20 mA
1
brown
+ 24 V transmitter supply
- internally
2
white
Transmitter output
supplied
3
blue
GND
4
black
Bridge after GND
4 – 20 mA
1
brown
not assigned
- externally
2
white
Process actual +
supplied
3
blue
not assigned
4
black
Process actual -
Frequency
1
brown
+ 24 V sensor supply
- internally
2
white
Clock input +
supplied
3
blue
Clock input - (GND)
4
black
not assigned
Frequency
1
brown
not assigned
- externally
2
white
Clock input +
supplied
3
blue
Clock input -
4
black
not assigned
Pt 100
1
brown
not assigned
(see infor-
2
white
Process actual 1 (current feed)
mation
3
blue
Process actual 2 (GND)
below)
4
black
Process actual 3 (compensation)
Tab. 14: Circular plug M8 - 4-pole (process actual value) - Type 8693
For reasons of wire compensation connect the Pt 100 sensor
via 3 wires. Always bridge Pin 3 and Pin 4 on the sensor.
Type 8692, 8693
Electrical installation
switch
Switch
on left
Switch
on right
Switch
on left
Switch
on right
Switch
on right
10.4. electrical installation devicenet
The Quickstart only describes the electrical installation of the posi-
tioner / process controller and the specification of the basic settings.
The settings of the bus communication are described in the
operating instructions for Type 8692 / 8693.
procedure:
Connect the positioner according to the tables.
The electrical connection module of types 8692 and 8693 features
a setscrew with nut which is used to connect the function earth (see
"Fig. 17: Connection DeviceNet").
Connect the setscrew to a suitable grounding point. For
ensuring electromagnetic compatibility (EMC), make sure that
the cable is as short as possible (max. 30 cm, Ø 1.5 mm2).
When the supply voltage is applied, the positioner / process con-
troller is operating.
Make the required basic settings and actuate the automatic
adjustment of the positioner / process controller, as described in
the chapter entitled "11. Start-up Type 8692".
The settings in the BUS.COMM menu item are described in
the operating instructions of type 8692 / 8693.