Warning!
Valve moves after electrical voltage has been connected!
After connecting the electrical voltage, the actuator moves to the
set end position!
• Never perform setting of the proximity switch while a process is
running!
Switch on supply voltage at the positioner / process controller
and proximity switch connector.
Move actuator to the top end position (CFA and I) or bottom end
position (CFB).
Using a screwdriver, set proximity switch at the setting screw to
end position.
→Switch off the pilot air.
→Switch off supply voltage at the unit and the proximity switch
connector.
Return jumper to home position ("Fig. 13").
3.
Attach electronics module and close body:
noTe!
Be careful not to damage the pins at the pcB!
• When installing the electronics module, observe positioning of
the pins to the PCB on the electronics module.
Attach electronics module carefully and insert the pins in the
PCB on the electronics module.
Type 8692, 8693
Electrical installation
Check that the seal is correctly positioned in the body casing.
Fig. 14: Position of the seal in the body casing
noTe!
damage or malfunction due to ingress of dirt and moisture!
To ensure protection class IP65 / IP 67:
• Screw in body casing to the stop.
Screw in body casing (with transparent cap) (assembly tool:
674077
).
8)
Switch on supply voltage at the unit and the proximity switch
connector.
Restart operation of positioner / process controller.
The assembly tool (674077) is available through your Bürkert
8)
sales office.