10.2.3. e lectrical installation with cable gland
procedure:
Unscrew the 4 screws at the cover and remove the cover. The
screw terminals are now accessible.
Push the cables through the cable gland.
Connect the wires.
noTe!
damage or malfunction due to penetration of dirt and humidity!
To ensure protection class IP65 / IP67:
• Tighten the union nut on the cable gland according to the cable
size or dummy plugs used (approx. 1.5 Nm).
• Close cover and crosswise tighten the 4 screws (maximum
torque 0.7 Nm).
When the supply voltage is applied, the positioner / process con-
troller is operating.
Make the required basic settings and actuate the automatic
adjustment of the positioner / process controller, as described in
the chapter entitled "11. Start-up Type 8692".
26
english
Type 8692, 8693
Electrical installation
1
5
2
6
3
7
4
Fig. 15: Installation with cable gland
terminal
configuration
11
Set-point value +
10
Set-point value GND
14
Supply voltage +
13
Supply voltage
12
Binary input +
9)
13
Binary input GND
9)
9
Analogue position feedback +
9)
8
Analogue position feedback GND
9)
5
Binary output 1
9)
6
Binary output GND
9)
7
Binary output 2
9)
Tab. 10: Installation with cable gland
Option only.
9)
Switch
8
12
9
13
10
14
11
Screw terminals
(0/4 – 20 mA / 0 – 5/10 V)
24 V DC
GND