10.2.3. e lectrical installation with cable gland
procedure:
→
Unscrew the 4 screws at the cover and remove the cover. The
screw terminals are now accessible.
→
Push the cables through the cable gland.
→
Connect the wires.
noTe!
damage or malfunction due to penetration of dirt and humidity!
To ensure protection class IP65 / IP67:
• Tighten the union nut on the cable gland according to the cable
size or dummy plugs used (approx. 1.5 Nm).
• Close cover and crosswise tighten the 4 screws (maximum
torque 0.7 Nm).
When the supply voltage is applied, the positioner / process con-
troller is operating.
→
Make the required basic settings and actuate the automatic
adjustment of the positioner / process controller, as described in
the chapter entitled "11. Start-up Type 8692".
26
english
Type 8692, 8693
Electrical installation
1
5
2
6
3
7
4
Fig. 15: Installation with cable gland
terminal
configuration
11
Set-point value +
10
Set-point value GND
14
Supply voltage +
13
Supply voltage
12
Binary input +
9)
13
Binary input GND
9)
9
Analogue position feedback +
9)
8
Analogue position feedback GND
9)
5
Binary output 1
9)
6
Binary output GND
9)
7
Binary output 2
9)
Tab. 10: Installation with cable gland
Option only.
9)
Switch
8
12
9
13
10
14
11
Screw terminals
(0/4 – 20 mA / 0 – 5/10 V)
24 V DC
GND