Process actual value - Type 8693
input type
pin
configuration
6)
4 – 20 mA
1
+ 24 V transmitter supply
- internally
2
Transmitter output
supplied
3
Bridge after GND
4
GND
4 – 20 mA
1
not assigned
- externally
2
Process actual +
supplied
3
Process actual -
4
not assigned
Frequency
1
+ 24 V sensor supply
- internally
2
Clock input +
supplied
3
not assigned
4
Clock input - (GND)
Frequency
1
not assigned
- externally
2
Clock input +
supplied
3
not assigned
4
Clock input -
Pt 100
1
not assigned
(see infor-
2
Process actual 1 (current feed)
mation
3
Process actual 2 (compensation)
below)
4
Process actual 3 (GND)
Tab. 11: Process actual value - Type 8693
For reasons of wire compensation connect the Pt 100 sensor
via 3 wires. Always bridge Pin 3 and Pin 4 on the sensor.
Can be adjusted by software.
10)
Type 8692, 8693
Electrical installation
switch
Switch on
left
Switch on
right
Switch on
left
Switch on
right
Switch on
right
10.3. e lectrical installation
ProfiBus dP
The Quickstart only describes the electrical installation of the posi-
tioner / process controller and the specification of the basic settings.
The settings of the bus communication are described in the
operating instructions for type 8692 / 8693.
procedure:
Connect the positioner / process controller according to the
tables.
The electrical connection module of types 8692 and 8693 features
a setscrew with nut which is used to connect the function earth. (see
"Fig. 16: Connection PROFIBUS-DP").
Connect the setscrew to a suitable grounding point. For
ensuring electromagnetic compatibility (EMC), make sure that
the cable is as short as possible (max. 30 cm, Ø 1.5 mm
When the supply voltage is applied, the positioner / process con-
troller is operating.
Make the required basic settings and actuate the automatic
adjustment of the positioner / process controller, as described in
the chapter entitled "11. Start-up Type 8692".