Herunterladen Inhalt Inhalt Diese Seite drucken

Overcurrent Protection; Control Modes - Regin OPTIGO OP10 Anleitung

Vorschau ausblenden Andere Handbücher für OPTIGO OP10:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Overcurrent protection

The controller OP10-230 shall be protected by a fuse in the building
installation. The maximum load of the controller, 1000 VA, suggests a
6 A fuse.
Follow table 1 below for connection.
Table 1. I/O connection terminals
Terminal
Designation
Operation
1
G
24 V AC
Optigo 10 only
2
G0
3
1
L
230 V AC
Optigo 10-230 only
2
3
N
10
Common
DO3
Relay
11
NO
230 V AC,
12
NC
1000 VA
13
GDO
Reference for DO1 and DO2
14
DO1
Digital output
15
DO2
Digital output
20
AGnd
Reference for AO1 and AO2
21
AO1
0...10 V DC output
22
AO2
0...10 V DC output
40
DI2
Digital input
41
DI+
Reference for DI1 and DI2
42
DI1
Digital input
43
UI+
Reference for UI1
44
UI1
Universal input PT1000 or Digital
50
AGnd
Reference for AI1
51
AI1
PT1000 temp. sensor input
52
AGnd
Reference for AI2
53
AI2
PT1000 temp sensor input
54
SPI
Input PT1000 setpoint device
For best protection against disturbances, a shielded twisted-pair cable
should be used for wiring the sensors. Ground the shield at one end.

Control modes

Optigo can be configured to any one of the following control modes:
1.
Supply air temperature control
The supply air temperature is kept at the setpoint value by controlling
the output signals on AO1 and AO2. A single PI control loop is used.
Connect the sensor to AI1, even if only using a room sensor.
2.
Supply air temperature control with outdoor compensation
The supply air temperature is kept at the setpoint value by control-
ling the output signals on AO1 and AO2. A single PI control loop is
used. The setpoint is automatically adjusted according to the outdoor
temperature.
3.
Cascade connected supply air control with room / extract air
temperature influence
An offset in room temperature will adjust the supply air temperature
setpoint so as to eliminate the room temperature offset. Control
loops with PI-control are used. The supply air temperature is
minimum and maximum limited. A supply temperature sensor and a
room/extract air sensor must be utilised.
4.
Radiator circuit control with outdoor curve
The water temperature setpoint is changed according to the outdoor
temperature. A single PI control loop is used. A room temperature
sensor can be added to give corrective action if the room tempera-
ture differs from the setpoint. Without a room sensor, the setpoint is
a parallel displacement of the curve. When using a room sensor, the
setpoint is a room setpoint. This is automatically set when confi-
guring control mode 4.
OPTIGO OP10, OP10-230
5.
Domestic hot water control
The water temperature is kept constant by controlling the output
signal on AO1. A single PID control loop is used.
Control modes 1, 2 and 3
For control modes 1, 2 and 3, the analogue outputs can be configured
to the following combinations:
AO1
AO2
Display symbols
1
Heating
-
\
2
Cooling
-
/
3
Heating
Cooling
\ /
4
Heating
Heating
\ \
5
Cooling
Cooling
/ /
6
Heating
Damper
\ /
7
Cooling
Damper
\ /
Note: For control modes 1, 2 and 3, the input for fan indication (DI1)
must be connected in order to start the control function, otherwise an
alarm, AL3, will be generated. The input must "follow" the fan output,
i.e. if the output closes, the input must also close.
G
1
Fan start
10
COM
G0
2
11
NO
3
12
NC
DI2
40
DI+
41
42
DI1
Alarm
13
G
UI+
43
DO
14
DO1
UI1
44
0
15
DO2
A
50
Y1
GND
20
A
+
AI1
51
GND
21
AO1
A
52
G0
GND
Y2
22
AO2
AI2
53
G
54
SPI
Y
Figure 1. Wiring example: OP10 with electric heating (for example via
PULSER-X/D or TTC25) and damper. Cascade control.
L
230 V AC
N
24 V AC
Extended running
Fan indication
High temp limit switch
°C
Supply air temp
°C
Room / Extract
air temp
2

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Optigo op10-230

Inhaltsverzeichnis