General Information

Technical Data

Burner characteristics
The NC4, NC6 and NC9 fuel-oil burners
are blast air units with one firing rate (all
or nothing).
They can be used on different types of
heat-generators. They are available in
one adjustable head length. For a given
generator, the suited burner can be
determined on demand.
They use fuel-oil with density 0.84 at
10°C and heating capacity
11.86kWh/kg.
These burners are approved to index of
protection IP40.
NC4 R101
daPa
12
10
8
6
4
2
0
18
15
25
35
Burner
Cell
Conical
turbulator
NC 4 R101
Ø 63/16-4
NC 4 H101
Ø 63/16-4
MZ 770S
NC 6 R101
Ø 63/16-6
lg. 44 mm
NC 6 H101
Ø 63/16-6
NC 9 H101
Ø 75/20-6
24

Packaging

The burner and cover are supplied in a
package weighing approximately 10kg
and which includes:
- a kit-bag of assembly accessories,
- a document folder containing:
- operating instructions,
- wiring diagram,
- boiler-room plate,
- guarantee certificate.
NC4 H101 / NC6 H/R101
mbar
daPa
1,2
12
1
10
0,8
8
0,6
6
0,4
4
0,2
2
0
0
20
40
15
25
45
Flow rate
Flame
power
kg/h
kW
1.5 - 3.4
18 - 40
slots
1.7 -3.4
20 - 40
slots
3.4 - 4.6
40 - 55
slots
3,4 - 4,6
40 - 55
slots
3.8 - 8
45 - 95
slots
04/2006 - Art. Nr. 13 010 551E
mbar
1,2
1
0,8
0,6
0,4
0,2
0
40
kW
35
45
55
65
Nozzle
Pre-heated
nozzle line
US gal/h
0.5 to 0.85
FPHB5
0.5 to 0.85
no
1 to 1.2
FPHB5
1 to1.2
no
1.25 to 1.75
no
Space requirements and dimensions
The minimum clearance on each side of
the burner should be at least 0.60 metre
for maintenance purposes.
Boiler-house ventilation
The volume of fresh air required is
1.2m3/kWh produced at the burner.
NC4
NC6
A
Min
273
273
Max
323
323
B
Min
70
Max
120
120
C
Ø
80
D
Min
21
Max
71
NC9 H101
daPa
12
10
8
6
4
2
0
45
40
50
60
70
80
Main components
• Control and safety unit: SH1xx
• Electric motor:
single-phase 230V, 50Hz, 2800min
85-110W, capacitor 4µF/400V
• Ignition transformer:
EBI 2 x 7.5kV
• Ventilation turbine:
NC4/6: Ø133x42
NC9: Ø133x62
• Air flap control: manual
• Fuel-oil pump with electrovalve:
AS47D
• Flame tube:
NC4/6: Ø63/80 x177
NC9: Ø75/90x192
NC9
297
357
70
70
138
80
90
21
15
71
83
mbar
1,2
1
0,8
0,6
0,4
0,2
0
95
kW
90
100
-1