CHIMNEY POT DISTANCES AND POSITIONING:
Roof slope
α α α α
15°
30°
45°
60°
7095802 Rev.01 – EN
10 m
>A
min. H
(1)Ridge axis
α
Distance between ridge and
chimney
A (m)
< 1.85 m
> 1.85 m
< 1.50 m
> 1.50 m
< 1.30 m
> 1.30 m
< 1.20 m
> 1.20 m
(1) If there are flues which are side by side, one
chimney pot must surpass the other by at least 50
cm in order to avoid pressure transfers between the
flues themselves.
(1) The chimney pot must not have obstacles within 10 m such
as walls, slopes or trees. If this is not the case, raise the pot by
at least 1 m above the obstacle.
The chimney pot must surpass the roof ridge by at least 1 m.
> _ A
0.5 m
(2)Roof
Minimum chimney height (measured from the
UNI 10683/98
outlet)
H (m)
0.50 m beyond the ridge
1.00 m from the roof
0.50 m beyond the ridge
1.30 m from the roof
0.50 m beyond the ridge
2.00 m from the roof
0.50 m beyond the ridge
2.60 m from the roof
Picture 7
Picture 8
Picture 9
27