Herunterladen Inhalt Inhalt Diese Seite drucken

Beretta Mynute Green 38 C.S.I. E Installationsanleitung Seite 18

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 113
ENGLISH
TECHNICAL DATA
DESCRIPTION
Heating
Heat input
Maximum heat output (80/60°)
Maximum heat output (50/30°)
Minimum heat input
Minimum heat output (80°/60°)
Minimum heat output (50°/30°)
Nominal Range Rated heat output (Qn)
Minimum Range Rated heat output (Qm)
DHW
Heat input
Maximum heat output (*)
Minimum heat input
Minimum heat output (*)
(*) average value of various DHW operating conditions
Useful efficiency (Pn max - Pn min)
Efficiency 30% (47° return)
Combustion performance
Useful efficiency Pn max - Pn min (50°/30°)
Useful efficiency 30% (30° return)
Average Range Rated efficiency Pn (80°/60°)
Average Range Rated efficiency Pn (50°/30°)
Electric power
Category
Country of destination
Power supply voltage
Degree of Protection
Pressure drops on flue with burner on
Pressure drops on flue with burner off
Heating operation
Pressure - maximum temperature
Minimum pressure for standard operation
Selection field of heating water temperature
Pump: maximum head available
for system capacity
Membrane expansion tank
Expansion tank pre-charge
DHW operation
Maximum pressure
Minimum pressure
Hot water quantity with ∆t 25°C
with ∆t 30°C
with ∆t 35°C
DHW minimum output
Selection field of DHW temperature
Flow regulator
Gas pressure
Methane gas nominal pressure (G20)
LPG liquid gas nominal pressure (G31)
Hydraulic connections
Heating input - output
DHW input-output
Gas input
18
Mynute Green 25 C.S.I. E
kW
25,00
kcal/h
21.500
kW
24,50
kcal/h
21.070
kW
26,25
kcal/h
22.575
kW
6,00
kcal/h
5.160
kW
5,89
kcal/h
5.067
kW
6,48
kcal/h
5.573
kW
25,00
kcal/h
21.500
kW
6,00
kcal/h
5.160
kW
25,00
kcal/h
21.500
kW
25,00
kcal/h
21.500
kW
6,00
kcal/h
5.160
kW
6,00
kcal/h
5.160
%
98 - 98,2
%
102,3
%
98,3
%
105 - 108
%
107,1
%
98,6
%
105,8
W
123
II2H3P
-
V - Hz
230 - 50
IP
X5D
%
1,73
%
0,11
bar - °C
3 - 90
bar
0,25 - 0,45
°C
20/45 - 40/80
mbar
300
l/h
1000
l
8
bar
1
bar
6
bar
0,15
l/min
14,3
l/min
11,9
l/min
10,2
l/min
2
°C
37 - 60
l/min
11
mbar
20
mbar
37
Ø
3/4"
Ø
1/2"
Ø
3/4"
Mynute Green 30 C.S.I. E
Mynute Green 38 C.S.I. E
30,00
25.800
29,10
25.026
31,62
27.193
6,00
5.160
5,90
5.072
6,46
5.557
30,00
25.800
6,00
5.160
30,00
25.800
30,00
25.800
6,00
5.160
6,00
5.160
97 - 98,3
103,1
97,2
105,4 - 107,7
108,9
97,7
106,4
129
II2H3P
-
230 - 50
X5D
2,82
0,10
3 - 90
0,25 - 0,45
20/45 - 40/80
300
1000
10
1
6
0,15
17,2
14,3
12,3
2
37 - 60
13
20
37
3/4"
1/2"
3/4"
30,00
25.800
29,31
25.207
31,95
27.477
7,00
6.020
6,85
5.888
7,51
6.459
30,00
25.800
7,00
6.020
38,00
32.680
38,00
32.680
7,00
6.020
7,00
6.020
97,7 - 97,8
102,4
97,9
106,5 - 107,3
108,2
98,1
106,8
153
II2H3P
-
230 - 50
X5D
2,15
0,12
3 - 90
0,25 - 0,45
20/45 - 40/80
300
1000
10
1
6
0,15
21,8
18,2
15,6
2
37 - 60
15
20
37
3/4"
1/2"
3/4"

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis