4 ac motor controller wm/drm 220-230v ac
Vorschau ausblenden Andere Handbücher für animeo IB+:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
GB
A
PICTURES
[1] IB+ 4 AC Motor Controller WM 220-230 V AC,
wall-mounted version
[2] IB+ 4 AC Motor Controller DRM 220-230 V AC,
DIN-rail version
B
MOUNTING
[1] Choose the optimal location: sufficient surface area
[2] Needed space for the DIN-rail version
1.
Mounted in an electrical cabinet
[3] Mounting of the IB+ 4 AC Motor Controller WM or DRM
[4] Use cable tie!
[5] Keep to minimum distance
C
WIRING
[1] Tool for all terminals
[2] Wiring diagram
[3] Check the correct running direction of the
endpro ducts (group and local control inputs).
UP: end product moves upward (C +s)
STOP: end product stops (C +t+s)
DOWN: end product moves downward (C +t)
n To close window press UP,
to open window press DOWN
[4] Possible switches
1.
Smoove Origin IB, Ref. 1811272
2.
Double push button unlocked
[5] Local control
One local push-button can control motors on
several Motor Controller.
CABLE
Connection to ...
Motors
Motor Controller Extensions
Switch
IB+ bus
220 - 230 V AC
Cables
Min.: 4 x 1.5 mm
/16 AWG
2
Max.: 4 x 2.5 mm
/13 AWG
2
Min.: 2 x 0.6 mm/19 AWG
Max.: 2 x 2.5 mm
/13 AWG
2
Min.: 3 x 0.6 mm/19 AWG
Max.: 3 x 2.5 mm
/13 AWG
2
Min.: 4 x 0.6 mm/19 AWG
Max.: 4 x 1.5 mm
/16 AWG
2
Min.: 3 x 0.75 mm
/16 AWG
2
Max.: 3 x 2.5 mm
/13 AWG
2
D
CONFIGURATION
[1] Reset / Prog button
With this button, you can access the basic
configuration of the Motor Controller.
[2] Selection of switch ergonomic
Local push button ergonomics and the type of
end products to be preselected:
• Screen mode (SCR)
• Venetian blind, European mode (default mode)
• Venetian blind, US mode
1.
To toggle between modes, press shortly the
Reset / Prog button. Repeat until the LED,
according to the desired configuration, lights up.
2.
Save and exit
[3] Factory RESET
[4] Learn running time/length
1.
Drive screen to upper end limit
2.
Press Stop until screen drives down on its own
3.
Press Stop when lower end limit is reached
[5] Learn and recall intermediate position (IP)
1.
Recording
2.
Recalling
[6] Symbols: actions
1.
Up
2.
Stop
[7] Symbols: end product status
1.
Up
2.
High position
3.
Down
4.
Low position
5.
Stop at the required position
6.
Short up and down movement
7.
Intermediate position (IP)
m When electronic motors are to be controlled through
this Motor Controller device it is mandatory to configure
the start-up delay time for electronic motors in the Motor
Controller settings. To configure the start-up delay time
WT Setting Tool Ref. 1811242 can be used.
Twisted pairs
Required
Recommended
Recommended
animeo IB+ 4 AC MOTOR CONTROLLER. REF. 5062280G -
Max. distance
150 m
50 m
100 m
1000 m