Herunterladen Inhalt Inhalt Diese Seite drucken

Operation; Environmental Conditions And Operating Limits; Technical Data; Mounting Information - Maico EC 30 E Montage- Und Betriebsanleitung

Deckenfächer
Vorschau ausblenden Andere Handbücher für EC 30 E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

UK │ 5. Operation

5. Operation

Switch fan On/Off with switch which is to be
provided by the customer. For speed control,
see Maico accessories.
In the event of thermal overload, the fan
switches off. Make sure to wait until the motor
has cooled down. Cool-down time can be up
to 30 minutes. CAUTION: The fan switches
back on automatically after cooling down.
6. Environmental conditions and
operating limits
● Permitted ambient and airstream
temperature:
40 °C /
EC 30 E: +
+ 55 °C /
EC 90 B:
● Information for operation with occasional
temperatures below -20° on request.
● Storage: Store unit exclusively in a dry
location (-20 to +50 °C).

7. Technical data

For more technical data,  rating plate.
For dimensions  Fig. A.
Rated voltage
Power frequency
Power consumption
I
max
Degree of protection
Weight
16
40 °C
EC 40 D: +
60 °C
EC 140 B: +
230 VAC
50 Hz
EC 30 E: 37 W
EC 40 D: 40 W
EC 90 B: 116 W
EC 140 B: 120 W
EC 30 E: 0.25 A
EC 40 D: 0.20 A
EC 90 B: 0.55 A
EC 140 B: 0.60 A
IP 20
EC 30 E: 2.5 kg
EC 40 D: 3.2 kg
EC 90 B: 5.3 kg
EC 140 B: 8.4 kg

8. Mounting information

● Permissible minimum installation height:
min. 2.3 m from the lower edge of the
impeller blades to the floor (as per
EN 60335-2-80).
● For recommended minimum distances
between several ceiling fans  planning
documents.
● Mounting material that is sufficiently
dimensioned and suitable for the surface is
to be supplied by the customer. For
hanging the fan, use a Ø 7 mm ceiling hook
with a strength class of 4.8.
● Select installation site where foreign bodies
will not be accidentally drawn in. Observe
installation height.
● Take the risk of draughts into account
when planning by selecting a suitable
installation location.
● To avoid sound bridges with the structure,
observe distances from other façade
components and, if necessary, use
isolating elements.
● The fan is speed controllable. Wiring
diagram for speed control on request.

9. Mounting

9.1 Mounting EC 30 E and EC 40 D
These ceiling fans are completed mounted ex
factory. For conversion to an optional, longer
fastening rod (0.5 m or 1 m)  chapter 10.
DANGER
Risk of injury in case of incorrect insta-
llation due to falling device parts. When
installing and also following a removal,
always use new lock nuts as per ISO 7042.
CAUTION
Malfunctioning, if the ceiling fans cannot
swing freely. Leave 5 to 8 mm space
between upper edge of canopy [4] and
ceiling.

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ec 40 dEc 90 bEc 140 b

Inhaltsverzeichnis