REFRIGERANT PIPING

4
3 REFRIGERANT PIPING
3.1. PIPING CONNECTION
3.1.1.
PIPING POSITION
Piping connection position is the following, which is
available from all directions, top, left or right.
Gas Piping
Liquid Piping
3.1.2.
PIPING CONNECTION SIZE
In case of R407C
Model RCI
Gas Piping
Liquid Piping
In case of R410A
Model RCI
Gas Piping
Liquid Piping
Liquid Piping
Gas Piping
Unit Body
(mm)
1.0/1.5
2.0
12.70
15.88
6.35
6.35
(mm)
1.0/1.5
2.0
12.70
15.88
6.35
6.35
Special instructions for R410A
As R410A pressure is about 1.4 times higher than R407C,
improper installation may cause a serious trouble.
It is necessary to use the copper pipes, size of flare pipe
ends and flare nuts as shown below.
Flare Pipe Dimensions
Nominal
Diameters
1/4
3/8
1/2
5/8
Thickness of Copper Pipes
Nominal
Outer
Diameters
Diameters
1/4
6.35
3/8
9.53
1/2
12.70
5/8
15.88
Flare Nut Dimensions
Nominal
Diameters
1/4
3/8
1/2
5/8
(mm)
A
Outer
+0/-0.4
Diameters
R407C
R410A
6.35
9.0
9.1
9.53
13.0
13.2
12.70
16.2
16.6
15.88
19.4
19.7
(mm)
R407C
R410A
0.80
0.80
0.80
0.80
0.80
0.80
1.00
1.00
(mm)
B
Outer
Diameters
R407C
R410A
6.35
17
17
9.53
22
22
12.70
24
26
15.88
27/29
29