1 NAME OF PARTS

RCIM
 

2 UNITS INSTALLATION

WARNING:
Check to ensure that the accessories are packed
-
with the indoor unit.
Do not install the indoor units outdoors. If installed
-
outdoors, an electric hazard or electric leakage will
occur.
Consider the air distribution from each indoor unit to
-
the space of the room, and select a suitable location
so that uniform air temperature in the room can be
obtained. It is recommended that the indoor units be
installed 2.3 to 3 meters from the floor level. If the
unit is installed higher than 3 meters, it is also
recommended that a fan be used to obtain uniform
air temperature in the room.
Avoid obstacles which may hamper the air intake or
-
the air discharge flow.
Pay attention to the following points when the indoor
-
units are installed in a hospital or other places
where there are electronic waves from medical
equipment, etc.
Do not install the indoor units where
-
electromagnetic wave is directly radiated to the
electrical box, remote control cable or remote
control switch.
No. Part Name
1
Fan
2
Fan Motor
3
Heat Exchanger
4
Distributor
5
Expansion Valve
6
Electric Control Box
7
Gas Refrigerant Connection
8
Liquid Refrigerant Connection
9
Drain Pipe Connection
10
Motor for Drain Discharge Mechanism
11
Float Switch
12
Drain Pan
13
Panel P-N23WAM
14
Air Inlet Grille
15
Air Filter
16
Air Outlet
17
Air Inlet
18
Cover for Corner Pocket
Prepare a steel box and install the remote control
-
switch in it. Prepare a steel conduit tube and wire
the remote control cable in it. Then connect the
ground wire with the box and tube.
Install a noise filter when the power supply emits
-
harmful noises.
This unit is exclusive non electrical heater type
-
indoor unit. It is prohibited to install an electrical
heater in the field.
Mount suspension bolts using M10 (W3/8) as size,
-
as shown below:
For Concrete Slab
150~160mm
I-Beam
Steel
Suspension Bolts
Anchor Bolt
(W3/8 or M10)
Do not put any foreign material into the indoor unit
-
and check to ensure that none exist in the indoor unit
before the installation and test running. Otherwise a
fire or failure, etc., may occur.
1
NAME OF PARTS
1
Wooden Bar
(60 mm to 90 mm Square)
Square
Concrete
Nuts
washers
Wooden Beam
Sling Bolt
(W3/8 or M10)