After power-up the display will show the installed software
version. After 5 seconds it will automatically revert back to
the service display.
POWER FAILURE
In the event of a power failure, the program will remain
stored in the NOVRAM® during an undefined period, while an
incorporated SuperCap will maintain the correct time of day
during a period of several hours; consequently, in case of
prolonged power failure, the time of day might not be
maintained; if this happens, the time of day will be reset to
8:00 when the power supply is re-established, while the
indication will flash, indicating that the time of day needs to
be set.
When the power failure occurs during the execution of an
automatic regeneration, the control valve will remain in its
last position; when the power supply is re-established, the
control valve will return to the service position, stay there for
60 sec. and restart a complete regeneration from the
beginning.
TIMER FAILURE
In the event of a timer failure, the display will show the
message:
Service Required
If powering off/on the appliance doesn't solve this problem,
professional service is required.
SERVICE MODE
In service mode the display shows:
Simplex, Duplex Parallel: the time of day and the
remaining capacity:
8:01
1000L -
Duplex Alternating: the systems status (Service or
Standby) and the remaining capacity:
Srvc
1000L -
Stdby
1000L -

ELECTRONIC CONTROL PANEL

function
to advance to the next
parameter
to increase the value of the
parameter
to decrease the value of the
parameter
REGENERATION MODE
In regeneration mode the display shows:
Simplex,
Duplex
regeneration time and remaining cycle time:
Rgn:123 CycY:456
Duplex Alternating: the total remaining regeneration
time and remaining cycle time:
Rgn:123 CycY:456
When the regeneration is finished, the system remains in
Standby, until the other system starts a regeneration:
Stdby
The control valve can be reset to service mode at any time by
pressing the scroll
through the regeneration cycles.
CHECKING THE FLOW METER
In case of water usage, the remaining capacity counter in the
service display will count back. This way the correct
functioning of the water meter can be verified.
MANUAL REGENERATION
It is possible to manually initiate a regeneration.
1. Press the scroll
shows:
Regen in 10 sec
If the control valve is left in this position, the count-
down timer will count down to 0 sec and start a
regeneration.
To cancel this mode, press the scroll
the countdown timer has reached 0 sec; the control
valve will return to the service mode.
2. Press the scroll
advance the control valve to the next regeneration cycle.
DRIVE MOTOR SPEED (only for PF-SOF1)
The drive motor of the control valve, that drives the valve
body to its different regeneration positions, will start-up at
low speed to reduce its noise level. To increase the speed of
the drive motor, simply press the scroll
the drive motor is activated.
Page 11
Parallel:
the
total
1000L -
button, as such manually advancing it
button repeatedly until the display
button before
button again if you want to manually
button as soon as
EN - English
remaining