Switch to the CPU with a modified configuration (see Section 10.2.5 for PCS7 or Section
10.4.6 for STEP7)
S
Transition to redundant system mode (see Section 10.2.6 for PCS7 or Section 10.4.7 for
STEP7)
S
Change and load the user program (see Section 10.2.7 for PCS7 or 10.4.8 for STEP7)
Adding Interface Modules in the Case of the Master and Standby Subsystems
S
Change the hardware configuration offline (see Section 10.2.2 for PCS7 or Section 10.4.2
for STEP7)
S
STEP7 only: Add to and load organization blocks (see Section 10.4.3)
S
Stop the standby CPU (see Section 10.2.3 for PCS7 or Section 10.4.4 for STEP7)
S
Switch off the power supply to the standby subsystem
S
Insert the external DP master interface and set up a new DP master system
S
Switch on the power supply to the standby subsystem again
S
Download the new hardware configuration to the standby CPU (see Section 10.2.4 for
PCS7 or Section 10.4.5 for STEP7)
S
Switch to the CPU with a modified configuration (see Section 10.2.5 for PCS7 or
Section 10.4.6 for STEP7)
S
Switch off the power supply to the standby subsystem
S
Insert the external DP master interface; set up the connection to the new master system
S
Switch on the power supply to the standby subsystem again
S
Transition to redundant system mode (see Section 10.2.6 for PCS7 or Section 10.4.7 for
STEP7)
S
Change and load the user program (see Section 10.2.7 for PCS7 or 10.4.8 for STEP7)
Removing Interface Modules in the Case of the Master Subsystem
S
Change the hardware configuration offline (see Section 10.3.1 for PCS7 or Section 10.5.1
for STEP7)
S
Change and load the user program (see Section 10.3.2 for PCS7 or Section10.5.2 for
STEP7)
A5E00073168-02
CPU 417-4H
17