the BENNING PV 1-1.
-
Switch on the BENNING CC 3 current clamp adapter and select the 40 A range.
-
Switch on the BENNING PV 1-1 and press the
clamp measurement is displayed.
-
For direct current (DC) measurements, press the null balance key (ZERO) of the
BENNING CC 3 until a current value of approx. 0 A is displayed.
-
Enclose the single-wire live conductor by means of the current clamp adapter.
-
The measured current will be shown on the display 1 .
See figure 8:
AC/ DC current measurement by means of optional current clamp adapter
BENNING CC 3
8.6 Measurement on several identical PV modules/ PV strings
For PV systems with several identical PV strings, the open-circuit voltages and short-circuit cur-
rents must be compared with each other at stable radiation conditions. The values should be
identical and should have a maximum deviation of 5 % (at stable radiation conditions). Moreover,
the measured values have to be compared with the values to be expected.
-
At the beginning of the series of measurements, press and hold the
-key 6 in order to delete the measured value memory.
-
Connect the first PV string of the PV generator to the BENNING PV 1-1.
-
Press the
-key 3 to start the automatic measurement of the first PV string.
Auto
-
Press the
-key 8 to store the measured values.
-
Connect the next PV string to the BENNING PV 1-1 and press the
automatic measurement.
-
Press the
-key 8 to store the measured values.
-
Repeat this procedure for all identical PV strings at stable radiation conditions.
-
After measurement, the stored measured values can be recalled pressing the
soon as a measured value deviates by more than 5 % from the average value of all stored
measured values regarding the open-circuit voltage or short-circuit current, the ">5%" sym-
bol O starts flashing.
-
To call the average values, press the
displayed. The average values of the open-circuit voltage and of the short-circuit current are
shown on the display 1 .
See figure 6:
Automatic solar panel measurement, ISO measurement via earthing conductor

8.7 Measured value memory

8.7.1
Storing measured values
The BENNING PV 1-1 can store up to 200 display screens. Depending on the measure-
ments carried out, the values for protective conductor resistance, open-circuit voltage, short-
circuit current, insulating resistance with testing voltage and even the measured AC/DC current
( BENNING CC 3) are stored with a date/ time stamp.
-
Press the
-key 8 to store the displayed measured values to the first free storage location.
Successful storage will be confirmed by the "STORE" symbol L on the LC display 1 .
8.7.2
Calling measured values
-
Press the
-key 6 to recall the stored measured values with the corresponding storage
location number N. The symbol "RECALL" M is displayed 1 . The storage location number
N is shown on the display 1 .
-
Press the
-key 6 to go to the previous storage location.
8.7.3
Deleting the measured value memory
-
To delete the entire measured value memory, press the
8.7.4
Warning in case of the measured value deviating by 5 %
-
In case the displayed measured value memory (open-circuit voltage and short-circuit cur-
rent) deviates by 5 % from the average value of all stored measured values, the "5%" symbol
starts flashing.
8.7.5
Average value of the entire measured value memory regarding the open-circuit voltage
and short-circuit current
-
Press the
-key 6 repeatedly until the storage location 0 N is shown on the display 1 .
The symbol "RECALL" M is displayed 1 .
-
The storage location 0 N calculates the average values for open-circuit voltage and short-
circuit current from all stored measured values.
8.7.6
Reading out the measured value memory via the USB interface
To read out the measured values via the USB interface 7 , you have to install the hardware driver
from the "Treiber-driver" directory on the enclosed CD-ROM and then the download program
from the CD-ROM's "Programm-program" directory on your PC once.
In order to download the data, please proceed as follows:
-
Disconnect all safety measuring leads from the BENNING PV 1-1.
-
Connect the BENNING PV 1-1 to your PC by means of the USB connecting cable.
-
The hardware driver is installed automatically on a free COM port and confirms that the new
hardware can be used.
09/ 2012
-key 3 until the
Auto
-key 6 repeatedly until the storage location 0 is
BENNING PV 1-1
symbol B for current
-key 8 and the
-key 3 to start the
Auto
-key 8 and the
-key 6 . As
-key 6 .
19