Reference conditions
Input current I
i
Input voltage U
i
Frequency f
i
Waveform
Ambient temperature T
Auxiliary voltage U
Warm-up time
External fields
Environmental conditions
Ambient Temperature
Operating Temperature Range 32 °F to 131 °F (0 °C to 55 °C)
Storage Temperature Range
Max. relative humidity
Max. altitude above sea level
Pollution degree
Additional Technical Data
Internal fuse
Internal fuse, secondary
Protection class according IEC 60529
Device
Front
Rear
Personnel protection
The stated error limits apply for
reference conditions
I
iN
U
iN
45 to 65 Hz
Sinus, harmonic distortion ≤ 5 %
23 °C ±1 °C
A
U
H
HN
≥ 15 min
no
The device is designed for indoor
use only
According to IEC 60688
-13 °F to 158 °F (-25 °C to 70 °C)
80 % for temperatures up to 31 °C
decrease linearly to 50 % at 40 °C
2000 m
2, no condensation
Not replaceable
Type T500 mA/250 V according
IEC 60127
Not replaceable
Type F2A/125 V according
UL 248-14
IP 20, IP 41 or IP 65 see ordering
data 2.4
IP 20
IP 1x
59
±1 %
±1 %
±1 %