4.2
2P AND 3P EARTH MEASUREMENT
4.2.1
DESCRIPTION OF THE FUNCTION
3P and 2P earth measurements are made in a power-off condition.
s are made in a power-off condition.
s are made in a power-of
The measurements are made with two auxiliary rods (3 poles) and one auxiliary rod (2 poles), respectively.
Note however that measurements with 2 auxiliary rods are more accurate.
Measurement in 3P mode: the instrument generates an alternating current square wave (128Hz) between
terminals H and E, then measures the voltage between terminals S and E: from this voltage and the current
generated, it deduces global earthing resistance R
Measurement in 2P mode: the instrument generates a signal between terminals H and E, measures the
voltage on terminal H, and deduces resistance R
4.2.2
PREP
PREPARA
PREPARA
ARATION FOR THE MEASUREMENT (CONNECTION)
ARA
TION FOR THE MEASUREMENT (CONNECTION)
=> In SET-UP
In SET-UP
In SET
-UP
-UP, set the value of the no-load volt
, set the value of the no-load volt
in a damp environment (see § 3.2).
=> If necessary,
adjust the alarm, R
PUSH
btn
>
88.88
88.88
88.88
PUSH
btn
activate the alarm by pressing the ALARM key and 2nd key after SET
An overshoot of an alarm threshold during a measurement is indicated by a continuous
audible signal
compensate the measuring cables (see § 3.3).
www.electronicaembajadores.com
.
E
.
E
age generated by the instrument: U
, in the SET
, in the SET-UP
, in the SET-UP
mode,
E ALARM
2
nd
MORE
direction of alarm (> ou<)
location of decimal point
setting of the values of each of the 4 digits,
selected by successive presses on the
keys
MORE
x3
key and 2nd key after SET
key and 2nd key af
59
= 50 V
= 50 V, or 25V
= 50 V, or 25V
L
ter SET
ter SET-UP
-UP
exit .