D Appendix D, Modbus TCP Information
The Modbus TCP server is running on the standard port number 502.
The server will respond on the following "slave address" or "Unit Identifier number".
Slave address or
Unit Identifier
1 (0x01)
2 (0x02)
3 (0x03)
4 (0x04)
33 (0x21)
34 (0x22)
35 (0x23)
The access rules are,
Access Rule
read
write
D.1 Data from Pluto
Modbus TCP slave address 33, (0x21), for read node status and combined data from each Pluto.
Note: Only 100 words can be read in one request!
If more data is needed divide them in two or more request with selected start/end address in the
request. For example a request with start 1 and end 66 will give node status and Pluto global data.
A request with start 67 and end 130 will give additional data.
Address
Data Name
1
Node Status
3
PLUTO 00
5
PLUTO 01
7
PLUTO 02
9
PLUTO 03
11
PLUTO 04
13
PLUTO 05
15
PLUTO 06
17
PLUTO 07
19
PLUTO 08
21
PLUTO 09
23
PLUTO 10
25
PLUTO 11
27
PLUTO 12
29
PLUTO 13
31
PLUTO 14
33
PLUTO 15
35
PLUTO 16
37
PLUTO 17
39
PLUTO 18
41
PLUTO 19
43
PLUTO 20
45
PLUTO 21
Data
Data to Pluto
Local Data Request
Serial Pass through Request
Gateway Configuration

Data from Pluto

Local Data Response
Serial Pass through Response
Modbus TCP function
03 (0x03) Read Holding Register
16 (0x10) Preset Multiple Registers
127
Access
Rule
read/write
read/write
read/write
write
read
read/write
read/write
Data Type
Addr + 0
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
UDINT
MSW
Addr + 1
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW
LSW