IMPORTANT : The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation
and conductors used.
A main switch or other means for disconnection, having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with relevant local and national legislation.
Model
Voltage range
Power supply cable size
Number of wire
Recommended fuse
All wires must be firmly connected.
All wires must not touch the water piping, or any moving parts
of the fan motor.
The connecting wires to the indoor unit must be clamped on
the wire clamps as shown in the figure.
The power supply cord must be equivalent to H05VV-F (60227
IEC 52 or 60227 IEC 53) which is the minimum requirement,
and to be used in protective tube.
FCU 3
VALVE N
N
2
1
3WV

ELECTRICAL WIRING CONNECTION

mm
2
A
FWT02~06AATNMV1
FCU 2
L
VALVE N
2
3WV
x1
Chiller
FWT02AATNMV1 /
FWT03AATNMV1 /
FWT04AATNMV1
220V – 240V/1Ph / 50Hz +
1.5
3
2
Wire Clamp
Interconnection
Cable
N
L
VALVE N
1
3WV
x2
5
FWT05AATNMV1 /
FWT06AATNMV1
1.5
3
2
Power Supply
FCU 1
N
L
2
1
N
T
S
R
x3
3WV
3 way valve
Relay (220-240V, 10A)
x1, x2, x3
Cable