Command Code & Return Data
Input Command:
GPAL <address> [CR]
Return Data from Power Supply:
Reading voltage [####] V [ON]
Reading current [####] A [ON]
Reading watt [####] W [ON]
Timer minute [####] second [##] timer [ON] colon [ON] m [ON] s [ON]
Setting voltage [###] V-const [ON] V-bar [ON] V [ON]
Setting current [###] I-Const [ON] I-bar [ON] A [ON]
Program [#] Program [ON] P-bar [ON]
SETTING [ON] Key lock [ON] Key open [ON] FAULT [ON] Output on
[ON]
Output off [ON] Remote [ON] [CR]
[OK] [CR]
Input Command:
VOLT <address> voltage {000-XXX} <CR>
Return Data from Power Supply:
[OK] [CR]
Input Command:
CURR <address> current {000-XXX} <CR>
Return Data from Power Supply:
[OK] [CR]
Input Command:
SOVP <address> voltage {000-XXX} <CR>
Return Data from Power Supply:
[OK] [CR]
Input Command:
SOUT <address> 1 <CR>
Return Data from Power Supply:
[OK] [CR]
Input Command:
SOUT <address> 0 <CR>
Return Data from Power Supply:
[OK] [CR]
Input Command:
POWW <address> location {1-9}0 <CR>
Return Data from Power Supply:
[OK] [CR]
Input Command:
POWW <address> location {1-9}1 <CR>
Return Data from Power Supply:
[OK] [CR]
Input Command:
PROM <address> location {1-9} Voltage {000-XXX} Current {000-
XXX} <CR>
Return Data from Power Supply:
[OK] [CR]
Description
Get LCD Display
Information
Set Voltage Level
XXX-Max. Output Rating
Voltage = XX.X V
Current = X.XX V
Set Current Level
Set upper Voltage Limit of PS
Disable Output of PS
Enable Output of PS
Enable the output when switch
on the power supply.
Disable the output when switch
on the power supply.
Set Voltage and Current
values of Preset
Memory
-52-