gation buttons (
) to go back to PS1
Level.
3.
If you do not use Ni1000 sensors, select the
PS2 level submenu by pressing SEL button,
to adapt the sensors configuration (units,
sensors type, temperature offset).
4.
If you have selected an application with auxil-
iary functions (REM, LIM, COMP, CAS,
MAXPRIO or WIN/SUM), select the PS3
level by pressing SEL button (
dedicated parameters :
Limitation and cascade functions:
- Maximum and Minimum values
- Proportional band and integration time
Winter / Summer change-over function set-
points
Compensation function, curve points
5.
Select PS4 level to finalize application set-
tings, displays depending on application se-
lected:
Q1 settings:
- Switching differential
- Minimum off time
Y1 settings:
- Proportional band
- Integration time
- End values
4/8
26.08.2009
Comfort and Economy setpoints for heating
and cooling
), to enter
6.
Quit the commissioning menu with EXIT PS
display by pressing the SEL button (
The application starts, all sensors will be
checked and existing sensors will be high-
lighted for future fault status messages.
Normal mode display appears with the main
sensor value (X1), progressive output value
(Y1) and relay output status (Q1) on display:
Notes:
• The commissioning level can be changed by
pressing the navigation buttons (
multaneously for 5 sec.
• Information displays are always available from
normal mode, by pressing one of navigation
buttons (
- Comfort setpoints (SP-...
- Economy setpoints (SP-... )
- Temperature sensor values
- Progressive output value (Y1)
- Relay output status (Q1)
- Actual application type