The symbols in the table below show the meter's operational status. The
status messages only appear in the main display (energy)! The temporary
display of the warning triangle can be caused by special operating sta-
tes and does not always mean that the device is malfunctioning. However,
should the symbol be displayed over a longer period of time, you should
contact the service company.
Symbol
Status
External voltage
Flow existent
Attention!
SSymbol flashing: Data transmission
Symbol constantly displayer: optical
interface active
Emergency operation
Code
Error
1
Temperature out of measuring range
2
Temperature out of measuring range
Short circuit return sensor
3
Interruption return sensor
4
Short circuit supply sensor
5
Interruption supply sensor
6
Battery voltage
7
Hardware error
8
Hardware error
9
10
Error in the measuring system
20
No water in the measuring tube
30
Reverse water flow detected
40
Air inside the medium
50
Measured value outside overload range Check dimensioning
100
Hardware error
800
Wireless interface
1000
Status end of the battery
2000
Status Initial verification expired
Error codes show faults detected by zelsius
error appears, the sum of the error codes is displayed: Error 1005 = error
1000 and error 5.
32
Français
Measure
Check system /device
for errors
Exchange device
Measure
Check sensors
Check sensors
Check sensors
Check sensors
Check sensors
Check sensors
Exchange device
Exchange device
Exchange device
Exchange device
Check operating pressure
Check installation position
Vent system
Exchange device
Exchange device
Exchange device respectively
battery
Exchange device
C5-CMF. If more than one
®
-
-
-
-