Siemens RWD82 Installationsanleitung Seite 4

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

to adapt the sensors configuration (units,
sensors type, temperature offset).
4.
If you have selected an application with auxil-
iary functions (REM, LIM, COMP, CAS,
MAXPRIO or WIN/SUM), select the PS3
level by pressing SEL button (
dedicated parameters :
- Limitation and cascade functions
- Maximum and minimum values
- Proportional band and integration time
Winter / Summer change-over function, set-
points
Compensation function, Curve points
5.
Select PS4 level to finalize application set-
tings, displays depending on application se-
lected:
Q1 and Q2 settings
- Switching differentials
- Minimum off time
3-position actuator settings
- Proportional band
- Integration time
- Cycle time
Comfort and Economy setpoints
6.
Quit the commissioning menu with EXIT PS
display by pressing the SEL button (
The application starts, all sensors will be
checked and existing sensors will be high-
lighted for future fault status messages.
Normal mode display appears with the main
sensor value (X1) and relay output status (Q1
and Q2) on display:
4/8
04.05.2009
Notes:
), to enter
• The commissioning level can be changed by
pressing the navigation buttons (
taneously for 5 sec.
• Information displays are always available from
normal mode, by pressing one of navigation
buttons (
- Comfort setpoint (SP-...
- Economy setpoint (SP-... )
- Temperature sensor values
- Relay outputs status (Q1 and Q2)
- Actual application type
).
CE1G3341de,en
) simul-
):
)
Siemens Building Technologies