DVEX roof fans

6.4.1
Preconditions
Only install the fan if the minimum air gap between the rotor and the nozzle is 4 ... 8 mm.
Installation position optional if not stated to the contrary.
Protective accessories must have been examined with a view to strength and material.
6.4.2
Assembly
WARNING
Danger from falling parts!
Check the underground (ceiling/wall) for strength before assembly,
when selecting the fi tting material, pay attention to the weight, vibration tendency and shearing
forces (weight, see name plate).
 Fit the fan on a fi rm base with suitable fi tting material
 Prepare the fan with hinged frame for connection and secure (see Fig. 9 A, B, C)
Close the fan carefully, do not drop it.
Secure it with an M 6x10 screw (2 screws from size 450 upwards).
Secure the two fl aps by means of an M 8x16 screw. They also act as protection against shutting.
 Fit the air connection lines and the accessories.
NOTE
The channel installation must be such that protection class IP 20 (contact distance rotating part < 12
mm) is fulfi lled on the admission side and protection class IP 10 (contact distance rotating part < 50
mm) can be guaranteed on the blow-out side.
6.4.2.1
Securing the hinged frame
 If a hinged frame is used, secure the DVEX fan as shown in Fig. 9.
M8x16
A
Fig. 9:
Secure DVEX fan