6

Assembly

NOTE
The safety information in Section 6 applies to all the fans described in these operating instructions.
6.1

Safety information

Keep to the following order in order to rule out the risk of injuries from rotating parts:
Assemble
Connect to energy
HAZARD
Hazard of explosion of an ignition-capable atmosphere!
On the intake side, a protective grid has been attached in order to rule out the risk from foreign bodies.
It guarantees a protection class of IP20.
On the pressure side, protection class IP 20 must be guaranteed by assembly of the fan in a duct/
channel system or by fi tting a protective grid.
Seal the system carefully.
Install accessory parts correctly.
Upstream or downstream components or those located directly in the air fl ow may not manifest any
unprotected aluminium or steel surfaces. Varnishing or a plastic coating fulfi lling at least grid section
characteristic 2 according to DIN EN ISO 2409 is necessary, in order to prevent an alumino-thermal
reaction.
Assembly may only be done by trained qualifi ed personnel paying attention to the relevant directives.
Comply with the system-related conditions and the requirements of the system manufacturer or plant builder.
Only install the fan when and if
the fan has not been damaged,
the fan wheel runs freely when turned by hand.
The fan housing may not be deformed during assembly.
Safety components, e.g. protective grids, may not be dismantled or circumvented or put out of function.
Install the fan with protection against dust, moisture and the infl uences of the weather.
Do not distort the fan housing in installation. Surfaces must be fl at.
Pay attention to the direction of fl ow (arrows).
For maintenance and repair, ensure secure access to the fan.
Provide for contact, intake protection and safety distances according to DIN EN 294 and DIN 24167-1.
Ensure uninhibited and even admission into the device and free blow-out.
In EX fans, the blade angle may not be amended subsequently.
In installation, guarantee that no vibrations are transferred to the duct/channel system or the housing frame of the
fan in operation. For this purpose, use connecting sleeves and fl anges from the accessories.
6.2

Axial fans AW-EX, AXC-EX and AXCBF-EX

6.2.1
Preconditions
AW-EX
Only install the fan if the distance between the fan wheel and the housing is constant.
AXC-EX and
Only install the fan if the minimum air gap between the blade tip and the housing matches the
AXCBF-EX
value of your fan in Table 11.