Beschreibung der Bausteine
3.2 Treiberbaustein DRV_3WL
Anschluss (Parameter)
U_L1_L2_QC
U_L2_L3
U_L2_L3_QC
U_L3_L1
U_L3_L1_QC
U_L1_N
U_L1_N_QC
U_L2_N
U_L2_N_QC
U_L3_N
U_L3_N_QC
PF_AVG
PF_AVG_QC
ACT_W
ACT_W_QC
KVA_TOT
KVA_TOT_QC
POS_CB
QDISCON
QOP_POS
QTEST_POS
QNO_CB
ST_CB
QNOT_RDY
QOFF
QON
QTRIP
QLOC_OFF
QRDY_ON
QUNV_REL
QSPR_CHAR
QOVLD_WRN
QSP_EXCEED
QWRN
QWR_PROT
QFREE_COM15
LST_TRIP
QTR_OVLD
QTR_ISC
38
Kommentar
Quality Code of U_L1_L2
Voltage line-to-line L2-L3 (B-C)
Quality Code of U_L2_L3
Voltage line-to-line L3-L1 (C-A)
Quality Code of U_L3_L1
Voltage star point L1-N (A-N)
Quality Code of U_L1_N
Voltage star point L2-N (B-N)
Quality Code of U_L2_N
Voltage star point L3-N (C-N)
Quality Code of U_L3_N
Power factor average
Quality Code of PF_AVG
Active energy in normal direction
Quality Code of ACT_W
Apparent power total
Quality Code of KVA_TOT
Position of circuit-breaker
1 = Disconnected
1 = Operating position
1 = Test position
1 = Circuit-breaker not present
Status of circuit-breaker
1 = Circuit-breaker not ready
1 = Main contacts disconnected
1 = Main contacts closed
1 = Circuit-breaker has tripped
1 = Local turn off of circuit-breaker
1 = Ready to switch on
1 = Voltage applied to undervoltage
release
1 = Storage spring is charged
1 = Overload warning present
1 = An activated setpoint value has been
exceeded
1 = A warning signal is currently present
1 = write operations are prohibited
1 = Status of the free user input on the
COM15 module
Reason for last trip
1 = Overload tripping (L)
1 = Instantaneous short-circuit (I)
Typ
Vor-
besetzung
BYTE
0
REAL
0.0
BYTE
0
REAL
0.0
BYTE
0
REAL
0.0
BYTE
0
REAL
0.0
BYTE
0
REAL
0.0
BYTE
0
REAL
0.0
BYTE
0
REAL
0.0
BYTE
0
REAL
0.0
BYTE
0
BYTE
0
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BYTE
0
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BYTE
0
BOOL
FALSE
BOOL
FALSE
Bausteinbibliothek SENTRON 3WL / 3VL für SIMATIC PCS 7
Funktionshandbuch, 11/2008, A5E02316905A-01
Art
B&B
O
O
x
O
O
x
O
O
x
O
O
x
O
O
x
O
O
x
O
O
x
O
O
x
O
O
x
O
x
O
O
O
x
O
x
O
O
O
O
O
x
O
O
O
O
O
O
O
O
O
O
O