Description of the functions
Intelligent stagnation flush:
DIP switch 4
Serves to rinse water supply lines in order to remove stagnant water that
accumulates during longer periods of non-usage.
"ON" position
= Intelligent stagnation flush activated (preset).
"OFF" position
= Intelligent stagnation flush deactivated.
0.5 - 24 h
10 - 180 s
40
Shower control
HyPlus
Time interval
Specifies the time between the stagnation
flushes.
Adjustable from 0.5 to 24 h at the interval
control (see p. 29).
Minimum flushing duration
Specifies the minimum flushing
duration at the set time interval.
Adjustable from 10 to 180 s at the
time control (see p. 29).
Intelligent stagnation flush
If the fitting has not been used in the set
interval at the very least for the set flushing
duration, stagnation flushing is triggered for
the remaining duration configured.
Otherwise stagnation flushing is not
performed.
WimTec PROOF S6 -
HyPlus
ON
OFF
1
2 3 4 5 6
Note
For visualisation of the
minimum flush duration,
see p. 42!