Safety shut-off valve 022
Start-up instructions
3
The sequence of start-up the SSV 022 is to be observed!
If the sequence is not considered, the valve disc arm contacts the inside of valve body and the
chamfered edge of valve disc arm (3) can be deformed .
a)  Pressure compensation by opening the manipulation valve (self closing) slowly, up to closing pressure of
regulator .
b)  Unscrew cap (8) of shut-off valve and pull the valve stem (2) by the aid of cap (8), to open the SSV (only
possible if pd smaller than OPSO and higher than UPSO).
c)  Hold the valve stem (2) for some seconds (it's necessary, that diaphragm and lever system can be locked
into operating position) .
d)  Unscrew cap of reset shaft on valve body . Turn the reset shaft (6) in direction of arrow*) until valve disc
arm (3) engages into latch lever .
e)  Screw on cap of reset shaft and valve stem .
*) For turning reset shaft (6), the maximum torque value is 5 Nm to engage valve disc arm (3) into latch lever .