Example 2:
Operating mode: cold / start temperature: 25 °C / stop temperature:
20 °C / max. flush time: 2 min. / max. number of flushings per day: 5
The temperature of 25 °C is exceeded. The HYGIENE BOX activates
a temperature flushing. If a temperature of 20 °C is reached within
2 min, the flushing stops. If the temperature of 20 °C fails to be
reached within 2 min., an error message appears and flushing stops.
If the device flushes more than 5 times within 24 hours, the device
activates an alarm and will not flush again for 24 hours.
Start temperature:
Defines the temperature above or below which flushing is activated.
Stop temperature:
Defines the temperature at which flushing stops.
Max. flush time:
Gibt die maximale Spüldauer an. Wird die Zieltemperatur innerhalb
der Spüldauer nicht erreicht, wird die Spülung gestoppt und ein
Alarm erscheint.
4.6.3. CYCLIC FLUSHING
The "cyclic flushing" function activates a flush in a definable interval.
The flush volume can also be defined. The flush time is calculated in
the same way as for stagnation flushing. Any water volume that has
flown between intervals will not be considered.
Example 1:
Interval: 6 hours / flush volume: 30 liters
Interval:
Specifies the time between flushing.
Flush volume:
The flush volume is the volume that is flushed after the interval.
4.6.4. MANUAL FLUSHING
Manual flushing is only intended for commissioning and can only be
activated directly on the device.
Flushing can be activated by pressing the button as follows: Press
and hold the button for approx. 3 seconds until the LED lights up
green.
The flush time is 1 minute.
During flushing, the LED flashes in yellow. To cancel the flush, the
same button function can be used as for starting the flush.
Setting parameters
Start temperature cold:
12 - 25 °C
Stop temperature cold:
10 - 23 °C
Flushing time:
30 Sek. - 10 Min.
Flushings / day:
1 - 20
Setting parameters
Interval:
10 min. - 30 days
Flush volume
1l - 100l
11