Menu P6  Setting additional programmes (Optional)
Submenu
Description
P60
Confirming the presence of a geothermal
exchanger (EWT).
• 0; G eothermal heat exchanger not fitted
• 1; Geothermal heat exchanger fitted
• 3; G eothermal heat exchanger unregulated.
If a valveless geothermal heat exchanger is fitted, then the unregulated setting must be
selected so that the ventilation unit's bypass valve continues to function properly.
P61
Setting the percentage by which the supply fan
must increase its speed when the valve of the
geothermal heat exchanger (EWT) is opened.
P62
Tge (= outside air temperature
for the geothermal heat exchanger), low
Note: The geothermal heat exchanger valve opens if the temperature falls below the set
temperature. The geothermal heat exchanger valve closes if the temperature rises above the
set temperature.
The geothermal heat exchanger valve only responds if the ventilation unit is in winter
mode.
P63
Tge (= outside air temperature for the
geothermal heat exchanger), high
Note: The geothermal heat exchanger valve opens if the temperature rises above the set
temperature. The geothermal heat exchanger valve closes if the temperature falls below the
set temperature.
The geothermal heat exchanger valve only responds if the ventilation unit is in summer
mode.
Tah (= temperature of the reheater),
P64
required
Note: The reheater will be deactivated once the set temperature has been reached.
Additional programme values
Minimum
Maximum
0 (= No)
3 (= Yes)
0%
99%
0%
15%
10%
25%
5%
40%
Factory reset
0
0%
7%
23%
18%
41 EN