Zehnder ComfoControl CC Luxe Installationsanleitung Seite 40

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Submenu
Description
P54
Confirming the presence of a bypass.
P55
Confirming the presence of a
(Optional)
reheater.
• 0; Reheater not fitted
• 1; R eheater fitted (analogue with 0-10V)
• 2; R eheater is fitted and is
regulated by a Pulse Width
Modulation (PWM) signal.
P56
Setting the required
air volume in the house.
• nL: "normal air volume".
• HL: "high air volume".
Note: Setting the air volume is the starting point for programming the air specifications and
setting the fans.
P57
Setting the type of ventilation unit.
• Li = "Left-hand version".
• Re = "Right-hand version".
Note:
The ventilation unit is correctly preprogrammed at the factory.
P58
Enter controller priorities.
• 0; P riority to highest setting
INCLUDING the signals from the
analogue (0-10V) inputs.
• 1; P riority to highest setting
EXCLUDING the signals from the
analogue (0-10V) ports.
P59
Confirming the presence of an
(Optional)
enthalpy exchanger.
• 0; Enthalpy exchanger fitted
• 1; E nthalpy exchanger with RH sensor.
• 2; E nthalpy exchanger without RH
sensor.
EN 40
The standard ventilation unit configuration includes a bypass. Leave the value at '1'.
This setting is lost during a factory reset and will then have to be reprogrammed. The
correct setting can be found on the ventilation unit's identification plate.
If an enthalpy exchanger without a sensor is selected, then the protection programme
will not be activated and malfunction alerts EA1 & EA2 will never occur.
Additional programme values
Minimum
Maximum
0 (= No)
1 (= Yes)
0 (= No)
1 (= Yes)
nL
HL
Li
Re
0
1
0 (= No)
2 (= Yes)
Factory reset
1
0
HL
Li
0
0