Herunterladen Diese Seite drucken

RECHNER SENSORS TRUE LEVEL Bedienungsanleitung Seite 17

Vorschau ausblenden Andere Handbücher für TRUE LEVEL:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 4
Adjustment instruction • Initial Operation
Check conditions for a correct adjustment:
The container is empty.
The probe is mounted according to the mounting instruction (page 12-13) and mechanically fixed.
Caution: Changing the position of the probe requires a new adjustment!
The electrical connection has been carried out correctly.
Caution: Take care that the colour marking of the probe cable is correct! - LED U
Remove the cover ot the amplifier (Adjusting elements see fig. 3 or printing inside of the cover.)
Abgleich:
Sensor montiert und angeschlossen, Behälter leer
Jumper Pos. 1 - Potentiometer 1 Schaltpunkt suchen
(LED A an / aus)
Jumper Pos. 2 - Potentiometer 2 Schaltpunkt suchen
(LED A an / aus)
Jumper Pos. 3 - Gerät ist in Betrieb
Ausgang /
Output
100...0 %
Zeitverzögerung /
Time delay
Füllstand /
Level
BE
Fig. 3 - The sequence of adjustment:
1. Plug the jumper below the LED A to the left in Pos. 1.
2. Turn the left potentiometer no. 1 to the right until the switch-on point of LED A is reached. If the LED is
already on, turn back to off-position and then search again for the switch-on point. Leave the potentiometer
near the switch-on point - LED on - (do not turn any further!).
3. Plug the jumper below the LED A to the right in Pos. 2.
4. Turn the right potentiometer no. 2 to the right until the switch-on point of LED A is achieved. If the LED is
already on, turn back to off-position and then search again for the switch-on point. Leave the potentiometer
near the switch-on point -LED on- (do not turn any further!).
5. Plug the jumper to Pos. 3 in the middle.
6. Adjustment is completed. The measuring system is ready for operation.
Caution: Please make the adjustment in the described order. Always start with Pos. 1!
During adjustment, please do not touch the coaxial terminals or have conductive tools come into contact
with them.
Do not adjust sealed potentiometers!
Adjustment:
Sensor mounted and connected, Container empty
Jumper Pos. 1 - Potentiometer 1 search measuring point
(LED A on / off)
Jumper Pos. 2 - Potentiometer 2 search measuring point
(LED A on / off)
Jumper Pos. 3 - Device in operation mode
Ausgang /
Output
0...100 %
1
Ausgang /
Füllstand /
Output
Level
Alarm:
Leer / Empty
Weiß /
White
LED A
2
1 3 2
Jumper
Koax
Schwarz /
Black
on.
B
17

Werbung