Knurr CoolTrans 100 kW Bedienungsanleitung Seite 7

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

CoolTrans
Manual / Bedienungsanleitung
2.
Operating Conditions
Purposeful Use
The device represents a heat transfer station for heat discharge via cooling water out of
water-cooled server cabinets.
The CoolTrans serves to separate the primary cooling water network from the secondary
cooling water network.
The pumps within the network have been designed to guaranty sufficient heat discharge
from the server cabinets.
In order to facilitate safe heat discharge, the connection (piping network) between the
CoolTrans and the equipment to be cooled needs to be designed according to the rules of
technology and to the performance parameters.
By means of diffusion-proof insulation, the installation of the CoolTrans itself is independent
of the humidity of ambient air.
The CoolTrans must be installed frost-proof.
The floor must be capable of bearing the CoolTrans load.
(distributed among four legs carrying lumped load each)
Temperature at the place of installation:
Absolute humidity at the place of installation:
Water temperature, flow, primary:
Water temperature, return, primary:
Temperature spread of water:
Application of antifreezers
in the cooling water:
Max. operating pressure:
Blowing-off pressure safety valve
Water connection, primary:
Water connection, secondary
Nominal voltage:
CoolTrans
01.998.362.0 / Ausgabe f
5°C to 35°C
Any
4°C - 8°C
(other temperature upon inquiry)
11°C - 14°C
(other temperature upon inquiry)
6K
Primary circuit up to 35%
Secondary circuit upon inquiry
Primary
16 bar
Secondary
6 bar
Secondary
2.5 bar
Possible from either side of the unit
Possible from either side of the unit
3 x 400V / 16A
50 Hz to 60 Hz
page / Seite7/80