CoolTrans
Manual / Bedienungsanleitung
5.2
Examples for Mounting Hydraulic Connections
Up to five CoolTrans modules of a total capacity of 500 kW can jointly be installed.
Connection is made by flanges DN 100, PN 16.
A) Serial arrangement of CoolTrans with intermediately arranged distribution modules
Up to a maximum of five CoolTrans modules with intermediately arranged distribution
modules.
The CoolTrans can optionally be connected from either their left or their right to the network
in the building.
Also, redundant connection from both sides to two separate cooling water circuits is
possible.
CTU
distributor
C TU
B) Serial arrangement of CoolTrans with an overall distribution unit
Up to a maximum of five CoolTrans modules with a connected optional distribution unit.
The distribution unit will be adapted to the desired number of cooling water circuits
CTU
CTU
CoolTrans
CTU
distributor
Cooling water secondary network
Cooling water primary network
CTU
CTU
Cooling water secondary network
Cooling water primary network
01.998.362.0 / Ausgabe f
CTU
distributor
CTU
distributor
CTU
distributor
.
page / Seite17/80